產(chǎn)品簡介
隨著石油、化工、軍工、工程、廠礦、礦業(yè)等產(chǎn)業(yè)的飛速發(fā)展,防爆配電箱在生產(chǎn)、倉儲、救援中的使用越來越廣泛,品種越來越多。在爆炸性氣體危險場所里如何防止防爆配電箱事故性爆炸的發(fā)生已經(jīng)成為十分重要的課題。由于防爆配電箱在工作時不可避免地產(chǎn)生電火花,它們一旦與生產(chǎn)或救援現(xiàn)場的爆炸性氣體混合物相遇,就會導(dǎo)致爆炸事故的發(fā)生,直接危及國家財產(chǎn)和公民的生命安全。因此,作為使用*廣泛的照明燈具,它的防爆技術(shù)問題早已引起了人們的普遍關(guān)注和高度重視。
適用范圍
1、爆炸性氣體混合物危險場所:1區(qū)、2區(qū)。
2、性氣體混合物:ⅡA、ⅡB、ⅡC。
3、可燃性粉塵環(huán)境20區(qū)、21區(qū)、22區(qū)
4、溫度組別:T1~T6。
5、防爆標(biāo)志:ExdeⅡBT6、*ExdeⅡCT6。
5.具體概括使用場所如室內(nèi),外工作場所,中國煤炭行業(yè),中石油,中石化,中海油,電力,治 金,鐵路,鋼鐵,船舶,部隊,航空航天,公安消防,化工,政府部門,場館,交通運輸,及大 型企業(yè)適用需要。 注:要求ⅡC級請注明。
Introduction
With the rapid development of the petroleum, chemical, military , engineering , industrial , mining and other industries, explosion-proof enclosures for use in the production , storage, rescue and more widely, more and more varieties . In places where hazardous explosive gas -proof distribution box on how to prevent accidental explosions have become a very important topic . Since the proof distribution box inevitably spark at work , once with explosive gas mixtures are produced or rescue scene of the encounter , it will lead to explosion occurred directly endanger the safety of life and property of the citizens of the country . Therefore, as the most widely used lighting, explosion-proof technical problems it had aroused widespread concern and attention.
Scope
An explosive gas mixtures dangerous places: 1 Zone 2 .
2 gas mixture : Ⅱ A, Ⅱ B, Ⅱ C.
3 , combustible dust Zone 20 , Zone 21 , Zone 22
4, the temperature groups : T1 ~ T6.
5 , proof mark : Exde Ⅱ BT6, * Exde Ⅱ CT6.
5 Specific summarized using places such as indoor and outdoor workplaces, China 's coal industry , PetroChina, Sinopec, CNOOC, electricity , metallurgy , railway , steel , shipbuilding , military , aerospace, public security and fire , chemical, government departments, venues, transportation transportation, and large enterprises need apply . Note: Please specify the requirements Ⅱ C grade .
防爆配電箱技術(shù)特點
1.鋁合金外殼壓鑄成型,表面噴塑,外形美觀;
2.內(nèi)裝C65N、NC100H及S25□S高分?jǐn)嘈⌒蛿嗦菲、M611或GV2電動機保護(hù)器、3VE1空氣開關(guān)CM1塑殼斷路器及信號燈等元件;
3.具有過載、短路保護(hù)功能;
4.模塊結(jié)構(gòu),各種回路可根據(jù)用戶需要自由組裝;
5.可根據(jù)用戶要求特制,如加裝電涌保護(hù)器、電流表、電壓表等;
6.鋼管貨電纜布線;
防爆配電箱技術(shù)參數(shù)
1.執(zhí)行標(biāo)準(zhǔn):GB3836.1、GB3836.2、GB3836.3、GB12476.1、IEC60079
2.防爆標(biāo)志:Exd II BT6、Exd II CT6
3.額定電壓:AC220/380V
4.主回路額定電流:1A、3A、5A、10A、15A、20A、25A、32A、40A、50A、60A
5.防護(hù)等級:IP54(IIB)、IP55(IIC)、IP65(DIP)
6.防腐等級:WF1
防爆配電箱型式試驗
型式試驗的目的是驗證定型的配電箱的設(shè)計性能是否符合本企業(yè)標(biāo)準(zhǔn)要求。
型式試驗是新產(chǎn)品試制投產(chǎn)必須進(jìn)行的試驗。只有當(dāng)產(chǎn)品設(shè)計、制造工藝、使用原材料或零部件結(jié)構(gòu)有更改,可能影響配電箱防爆性能時,才需要重新進(jìn)行有關(guān)項目的型式試驗。正常生產(chǎn)的產(chǎn)品每隔五年進(jìn)行一次。任一型式試驗的試品,從出廠檢驗合格的產(chǎn)品中,任意抽取2臺進(jìn)行試驗,2臺試品試驗都合格,才能認(rèn)為型式試驗合格。否則必須分析原因,采取技術(shù)措施甚至改進(jìn)設(shè)計、工藝等再重新進(jìn)行試驗,直到型式試驗合格為止。
型式試驗項目:
a) 所有出廠檢驗項目;
b) 溫升試驗、溫度試驗;
c) 外殼和透明件沖擊試驗;
d) 透明件耐熱試驗及耐寒試驗;
e) 彈性密封圈材料老化試驗;
f) 電纜引入裝置夾緊試驗;
g) 隔爆外殼耐壓試驗;
h) 隔爆外殼內(nèi)部點燃的不傳爆試驗;
i) 外殼防護(hù)能力試驗;
j) 操作性能試驗;
k) 漏電斷路器額定剩余動作電流,額定剩余不動作電流的*大分?jǐn)鄷r間試驗;
l) 脫扣器動作特性試驗;
m) 額定短路分?jǐn)嗄芰υ囼灐?br />
德力西防爆配電箱安裝與使用
1.安裝使用產(chǎn)品前應(yīng)檢查銘牌上的技術(shù)數(shù)據(jù)與使用情況是否相符;
2.安裝及維修前必須切斷前級電源;
3.進(jìn)、出線電纜穿過橡膠密封圈,須用墊圈及壓緊螺母壓緊,保證密封及電纜不得松動;
4.密封圈在使用過程中出現(xiàn)腐蝕、脆裂、變形、發(fā)粘或硬度變化超過出廠時的20%應(yīng)及時向廠家進(jìn)行選購并更換, 以確保防爆性能可靠;
5.維護(hù)拆卸時注意隔爆面不得磕碰、劃傷、腐蝕,并定期涂204-1防銹油;
6.配電箱在使用過程中要定期檢查,以保證其良好運行;
7.非*人員嚴(yán)禁開蓋維修、檢查。
Explosion-proof power distribution box Technical Features
1 aluminum die-casting, surface spray , beautiful appearance ;
2 built- C65N, NC100H and S25 □ S MCB , M611 or GV2 motor protection , 3VE1 CM1 MCCB air switch and lights and other components ;
3 with overload, short circuit protection ;
4 module structure, each circuit can be assembled freely according to user needs ;
5 specially designed according to user requirements , such as the installation of surge protectors, ammeter , voltmeter , etc. ;
6 steel goods cabling ;
Explosion-proof power distribution box Technical Data
1 Executive Standard :. GB3836.1, GB3836.2, GB3836.3, GB12476.1, IEC60079
2 Ex-mark :. Exd II BT6, Exd II CT6
3 Rated voltage :. AC220/380V
4 Main circuit Rated current :. 1A, 3A, 5A, 10A, 15A, 20A, 25A, 32A, 40A, 50A, 60A
5 Protection class :. IP54 (IIB), IP55 (IIC), IP65 (DIP)
6 corrosion grade :. WF1
Explosion-proof distribution box type test
The purpose of the type test is to verify design performance stereotypes distribution box meets the standard requirements of the enterprise .
Type test is to test new product trial production must be carried out . Only when the product design , manufacturing processes, use of raw materials or components structure changes that may affect the distribution box explosion-proof performance , only need to re- type test of the projects . Normal products once every five years . Any type test sample from the factory inspection of products, the random selection of two test , two sample tests are qualified to consider the type test qualified. Otherwise, you must analyze the causes and take technical measures to even improve the design, technology and other re- test until the type test so far.
Type test items:
a) All factory inspection program ;
b) temperature rise test , temperature test ;
c) impact test pieces of shell and transparent ;
d) transparent pieces of heat and cold test test ;
e) an elastic ring material aging tests ;
f) cable entry clamp test ;
g) flameproof enclosure pressure test ;
h) flameproof enclosure without internal ignition booster test ;
i) enclosure protection test ;
j) operating performance test ;
k) leakage circuit breakers rated residual operating current, the rated residual non-operating current maximum breaking time trials ;
l) release action performance test ;
m) rated short-circuit breaking capacity tests.
West Germany -proof distribution box installation and use
1 using the product should be checked before installation and use of technical data on the nameplate matches ;
(2) must be pre- cut power before installation and maintenance ;
3 inlet , outlet cable through the rubber seals, gaskets and compression nut must be pressed with a guarantee seal and cables must not loose ;
4 ring appeared in the course of corrosion, embrittlement , deformation, 20% more than sticky or hardness changes should be promptly shipped to manufacturers for the purchase and replacement to ensure reliable proof performance ;
5 Note that proof surface while maintaining the demolition shall bump , scratches , corrosion, and regularly painted rust oil 204-1 ;
6 distribution box during use should be checked periodically to ensure its good run ;
7 non-professionals prohibited openings maintenance and inspection.